- Table 4 to Subpart IIII of Part 60—Emission Standards for Stationary Fire Pump Engines

[As stated in §§ 60.4202(d) and 60.4205(c), you must comply with the following emission standards for stationary fire pump engines]

Maximum engine power Model year(s) NMHC + NOXCO PM KW<8 (HP<11)2010 and earlier10.5 (7.8)8.0 (6.0)1.0 (0.75) 2011 + 7.5 (5.6)0.40 (0.30) 8≤KW<19 (11≤HP<25)2010 and earlier9.5 (7.1)6.6 (4.9)0.80 (0.60) 2011 + 7.5 (5.6)0.40 (0.30) 19≤KW<37 (25≤HP<50)2010 and earlier9.5 (7.1)5.5 (4.1)0.80 (0.60) 2011 + 7.5 (5.6)0.30 (0.22) 37≤KW<56 (50≤HP<75)2010 and earlier10.5 (7.8)5.0 (3.7)0.80 (0.60) 2011 + 14.7 (3.5)0.40 (0.30) 56≤KW<75 (75≤HP<100)2010 and earlier10.5 (7.8)5.0 (3.7)0.80 (0.60) 2011 + 14.7 (3.5)0.40 (0.30) 75≤KW<130 (100≤HP<175)2009 and earlier10.5 (7.8)5.0 (3.7)0.80 (0.60) 2010 + 24.0 (3.0)0.30 (0.22) 130≤KW<225 (175≤HP<300)2008 and earlier10.5 (7.8)3.5 (2.6)0.54 (0.40) 2009 + 34.0 (3.0)0.20 (0.15) 225≤KW<450 (300≤HP<600)2008 and earlier10.5 (7.8)3.5 (2.6)0.54 (0.40) 2009 + 34.0 (3.0)0.20 (0.15) 450≤KW≤560 (600≤HP≤750)2008 and earlier10.5 (7.8)3.5 (2.6)0.54 (0.40) 2009 +4.0 (3.0)0.20 (0.15) KW>560 (HP>750)2007 and earlier10.5 (7.8)3.5 (2.6)0.54 (0.40) 2008 + 6.4 (4.8)0.20 (0.15)

1 For model years 2011-2013, manufacturers, owners and operators of fire pump stationary CI ICE in this engine power category with a rated speed of greater than 2,650 revolutions per minute (rpm) may comply with the emission limitations for 2010 model year engines.

2 For model years 2010-2012, manufacturers, owners and operators of fire pump stationary CI ICE in this engine power category with a rated speed of greater than 2,650 rpm may comply with the emission limitations for 2009 model year engines.

3 In model years 2009-2011, manufacturers of fire pump stationary CI ICE in this engine power category with a rated speed of greater than 2,650 rpm may comply with the emission limitations for 2008 model year engines.