Collapse to view only §§ 49.5516-49.9860 - §[Reserved]
Implementation Plan for the Gila River Indian Community
Implementation Plan for the Navajo Nation
Implementation Plan for the Pechanga Band of Luiseño Mission Indians of the Pechanga Reservation
Implementation Plan for the Salt River Pima-Maricopa Indian Community
Implementation Plan for the Gila River Indian Community
§ 49.5511 - Identification of plan.
(a) Purpose and scope. This section contains the approved implementation plan for the Gila River Indian Community dated August 2008. The plan consists of programs and procedures that cover general and emergency authorities, ambient air quality standards, permitting requirements for minor sources of air pollution, enforcement authorities, procedures for administrative appeals and judicial review in Tribal court, requirements for area sources of fugitive dust and fugitive particulate matter, general prohibitory rules, and source category-specific emission limitations and standards.
(b) Incorporation by reference.
(1) Material listed in paragraph (c) of this section was approved for incorporation by reference by the Director of the Federal Register in accordance with 5 U.S.C. 552(a) and 1 CFR part 51. Material is incorporated as it exists on the date of the approval, and notice of any change in the material will be published in the
(2) EPA Region IX certifies that the rules/regulations provided by EPA in the TIP compilation at the addresses in paragraph (b)(3) of this section are an exact duplicate of the officially promulgated tribal rules/regulations which have been approved as part of the Tribal Implementation Plan as of January 19, 2011.
(3) Copies of the materials incorporated by reference may be inspected at the Region IX Office of EPA at 75 Hawthorne Street, San Francisco, CA 94105-3901 or call 415-947-4192; the U.S. Environmental Protection Agency, EPA Docket Center (EPA/DC), Air and Radiation Docket and Information Center, MC 2822T, 1200 Pennsylvania Avenue, NW., Washington, DC 20460 or call 202-566-1742; and the National Archives and Records Administration. For information on the availability of this material at NARA, call 202-741-6030, or go to: http://www.archives.gov/federal_register/code_of_federal_regulations/ibr_locations.html.
(c) EPA-approved regulations.
EPA-Approved Gila River Indian Community Tribal Regulations
Tribal citation | Title/subject | Tribal effective date | EPA approval date | Explanations | Gila River Indian Community, Tribal Implementation Plan, Part I, General Provisions, Sections 1-3 | Definitions, General Authority, Procedures for Preparation, Adoption, and Submittal of the Air Quality Management Program | August 20, 2008 | 3/28/11 [76 FR 17028] | Gila River Indian Community, Tribal Implementation Plan, Part I, General Provisions, Section 4 | Adoption of National Ambient Air Quality Standards as Community Standards | August 20, 2008 | 3/28/11 [76 FR 17028] | Note: several revisions to the NAAQS have occurred since the adoption of the TIP. | Gila River Indian Community, Tribal Implementation Plan, Part II, Permit Requirements | Definitions, Applicability of Permit Requirements, Non-Title V Permit Requirements, Permit Revisions at a Non-Title V Source, Continuous Emissions Monitoring, Stack Height Limitation, Confidentiality of Information, Permit Fees | August 20, 2008 | 3/29/11 [76 FR 17028] | Title V regulations are not approved into the TIP. | Gila River Indian Community, Tribal Implementation Plan, Part III, Enforcement Ordinances | Civil Enforcement, Criminal Enforcement, Citizen Suits | August 20, 2008 | 3/28/11 [76 FR 17028] | Gila River Indian Community, Tribal Implementation Plan, Part IV, Administrative Appeals | General Provisions, Definitions, Administrative Appeals Procedures, Final Administrative Decision: Review, Judicial Review of Final Administrative Decisions | August 20, 2008 | 3/28/11 [ 76 FR 17028] | Gila River Indian Community, Tribal Implementation Plan, Part V, Area Source Emission Limits, Sections 1-2 | Open Burning, General Requirements for Fugitive Dust-Producing Activities | August 20, 2008 | 3/28/11 [76 FR 17028] | Gila River Indian Community, Tribal Implementation Plan, Part VI, Generally Applicable Individual Source Requirements for Existing and New Sources, Sections 1-3 | Visible Emissions; VOC Usage, Storage, and Handling; Degreasing and Solvent Metal Cleaning | August 20, 2008 | 3/28/11 [76 FR 17028] | Gila River Indian Community, Tribal Implementation Plan, Part VII, Source/Category Specific Emission Limits for Existing and New Sources, Sections 1-3 | Secondary Aluminum Production, Aerospace Manufacturing and Rework Operations, Nonmetallic Mineral Mining and Processing | August 20, 2008 | 3/28/11 [76 FR 17028] |
---|
(d) Nonregulatory.
Name of nonregulatory TIP provision | Tribal submittal date | EPA approval date | Explanations | Gila River Indian Community, Tribal Implementation Plan, Introductory Materials | June 22, 2009 | 3/28/11 [76 FR 17028 | Technical Amendments to Part II of the 2006 Air Quality Management Program Plan, Title 17 Chapter 9 of the Gila River Indian Community Law and Order Code | June 22, 2009 | 3/28/11 [76 FR 17028] | Minor NSR program support documents. | Minor New Source Review Demonstration | June 22, 2009 | 3/28/11 [76 FR 17028] | Minor NSR program support documents. | Letter from Margaret Cook, Executive Director, GRIC DEQ, to Deborah Jordan, Air Division Director, EPA Region 9, Re: Gila River Indian Community Tribal Implementation Plan | July 17, 2010 | 3/28/11 [76 FR 17028] | Letter discussing intent of citizen suit provisions in Part III. |
---|
Implementation Plan for the Navajo Nation
§ 49.5512 - Federal Implementation Plan Provisions for Four Corners Power Plant, Navajo Nation.
(a) Applicability. The provisions of this section shall apply to each owner or operator of the coal burning equipment designated as Units 1, 2, 3, 4, and 5 at the Four Corners Power Plant (the Plant) on the Navajo Nation Indian Reservation located in the Four Corners Interstate Air Quality Control Region (see 40 CFR 81.121).
(b) Compliance Dates. Compliance with the requirements of this section is required upon the effective date of this rule unless otherwise indicated by compliance dates contained in specific provisions.
(c) Definitions. For the purposes of this section:
(1) Affirmative defense means, in the context of an enforcement proceeding, a response or defense put forward by a defendant, regarding which the defendant has the burden of proof, and the merits of which are independently and objectively evaluated in a judicial or administrative proceeding.
(2) Air pollution control equipment includes baghouses, particulate or gaseous scrubbers, and any other apparatus utilized to control emissions of regulated air contaminants which would be emitted to the atmosphere.
(3) Business Day. Business day means a normal working day, excluding weekends and Federal Holidays.
(4) Daily average means the arithmetic average of the hourly values measured in a 24-hour period.
(5) Excess emissions means the emissions of air contaminants in excess of an applicable emissions limitation or requirement.
(6) Heat input means heat derived from combustion of fuel in a Unit and does not include the heat input from preheated combustion air, recirculated flue gases, or exhaust gases from other sources. Heat input shall be in accordance with 40 CFR part 75.
(7) Malfunction means any sudden and unavoidable failure of air pollution control equipment or process equipment or of a process to operate in a normal or usual manner. Failures that are caused entirely or in part by poor maintenance, careless operation, or any other preventable upset condition or preventable equipment breakdown shall not be considered malfunctions. This rule provides an affirmative defense to actions for penalties brought for excess emissions that arise during certain malfunction episodes. An affirmative defense is not available if during the period of excess emissions, there was an exceedance of the relevant ambient air quality standard that could be attributed to the emitting source.
(8) Owner or Operator means any person who owns, leases, operates, controls, or supervises the Plant or any of the coal burning equipment designated as Units 1, 2, 3, 4, or 5 at the Plant.
(9) Oxides of nitrogen (NO
(10) Plant-wide basis means total stack emissions of any particular pollutant from all coal burning equipment at the Plant.
(11) Regional Administrator means the Regional Administrator of the Environmental Protection Agency (EPA) Region 9 or his/her authorized representative.
(12) Shutdown means the cessation of operation of any air pollution control equipment, process equipment, or process for any purpose. Specifically, for Units 1, 2, or 3, shutdown begins when the unit drops below 40 MW net load with the intent to remove the unit from service. For Units 4 or 5, shutdown begins when the unit drops below 300 MW net load with the intent to remove the unit from service.
(13) Startup means the setting into operation of any air pollution control equipment, process equipment, or process for any purpose. Specifically, for Units 1, 2, or 3, startup ends when the unit reaches 40 MW net load. For Units 4 or 5, startup ends when the unit reaches 400 MW net load.
(14) 24-hour period means the period of time between 12:01 a.m. and 12 midnight.
(d) Emissions Standards and Control Measures—(1) Sulfur Dioxide. No owner or operator shall discharge or cause the discharge of sulfur dioxide (SO
(i) 12.0 percent of the potential combustion concentration assuming all of the sulfur in the coal is converted to SO
(ii) 17,900 pounds of total SO
(2) Particulate Matter. No owner or operator shall discharge or cause the discharge of particulate matter from any coal burning equipment into the atmosphere in excess of 0.050 pounds per million British thermal unit (lb/MMBtu) of heat input (higher heating value), as averaged from three sampling runs, each at 60 minutes in duration, each collecting a minimum sample of 30 dry standard cubic feet.
(3) Dust. Each owner or operator shall operate and maintain the existing dust suppression methods for controlling dust from the coal handling and storage facilities. Within ninety (90) days after promulgation of this section, the owner or operator shall submit to the Regional Administrator a description of the dust suppression methods for controlling dust from the coal handling and storage facilities, flyash handling and storage, and road sweeping activities. Within 548 days of promulgation of this section each owner or operator shall not emit dust with an opacity greater than 20 percent from any crusher, grinding mill, screening operation, belt conveyor, or truck loading or unloading operation.
(4) Opacity. No owner or operator shall discharge or cause the discharge of emissions from the stacks of Units 4 and 5 into the atmosphere exhibiting greater than 20% opacity, excluding uncombined water droplets, averaged over any six (6) minute period, except for one six (6) minute period per hour of not more than 27% opacity.
(5) Oxides of nitrogen. No owner or operator shall discharge or cause the discharge of NO
(i) From either Unit 1 or 2 in excess of 0.85 lb/MMBtu of heat input per unit, and from either Units 3, 4, or 5 in excess of 0.65 lb/MMBtu of heat input per unit averaged over any successive thirty (30) boiler operating day period;
(ii) In excess of 335,000 lb per 24-hour period when coal burning equipment is operating, on a plant-wide basis; for each hour when coal burning equipment is not operating, this limitation shall be reduced. If the unit which is not operating is Unit 1, 2, or 3, the limitation shall be reduced by 1,542 lb per hour for each unit which is not operating. If the unit which is not operating is Unit 4 or 5, the limitation shall be reduced by 4,667 lb per hour for each unit which is not operating.
(e) Testing and Monitoring. Upon completion of the installation of continuous emissions monitoring systems (CEMS) software as required in this section, compliance with the emissions limits set for SO2 and NO
(1) The owner or operator shall maintain and operate CEMS for SO2, NO or NO
(2) Sulfur Dioxide. For the purpose of determining compliance with this section, the sulfur dioxide inlet concentration (in lb/MMBtu) shall be calculated using the daily average percent sulfur and Btu content of the coal combusted. The inlet sulfur concentration and Btu content shall be determined in accordance with American Society for Testing and Materials (ASTM) methods or any other method receiving prior approval from the Regional Administrator. A daily fuel sample shall be collected using the coal sampling tower conforming to the ASTM specifications. The analyses shall be done on the daily sample using ASTM methods or any other method receiving prior approval from the Regional Administrator.
(i) The inlet sulfur dioxide concentration shall be calculated using the following formula:
I(ii) The total pounds of SO
(3) Particulate matter. Particulate matter emissions shall be determined by averaging the results of three test runs. Each test run shall be sixty (60) minutes in duration and shall collect a minimum volume of thirty (30) dry standard cubic feet. Within six (6) months of promulgation of this section, particulate matter testing shall be conducted annually and at least six (6) months apart, with the equipment within 90 percent of maximum operation in accordance with 40 CFR 60.8 and appendix A to 40 CFR part 60. The owner or operator shall submit written notice of the date of testing no later than 21 days prior to testing. Testing may be performed on a date other than that already provided in a notice as long as notice of the new date is provided either in writing or by telephone or other means acceptable to the Region 9 Enforcement Office, and the notice is provided as soon as practicable after the new testing date is known, but no later than 7 days (or a shorter period as approved by the Region 9 Enforcement Office) in advance of the new date of testing.
(4) Oxides of nitrogen. The total daily plant-wide oxides of nitrogen emissions in pounds of NO
(5) Continuous emissions monitoring shall apply during all periods of operation of the coal burning equipment, including periods of startup, shutdown, and malfunction, except for CEMS breakdowns, repairs, calibration checks, and zero and span adjustments. Continuous monitoring systems for measuring SO
(6) The owner or operator shall maintain a set of opacity filters to be used as audit standards.
(7) Nothing herein shall limit EPA's ability to ask for a test at any time under Section 114 of the Clean Air Act, 42 U.S.C. 7414, and enforce against any violation.
(8) In order to provide reasonable assurance that the scrubbers for control of particulate matter from Units 1, 2, and 3 are being maintained and operated in a manner consistent with good air pollution control practice for minimizing emissions, the owner or operator shall comply with the following provisions:
(i) The owner or operator shall develop a plan to monitor, record, and report parameter(s) indicative of the proper operation of the scrubbers to provide a reasonable assurance of compliance with the particulate matter limits in paragraph (d)(2) of this section. The owner or operator shall submit this plan to the Regional Administrator no later than sixty (60) days after the effective date of this FIP. The owner or operator shall implement this plan within 90 days of approval by the Regional Administrator and shall commence reporting the data generated pursuant to the monitoring plan in accordance with the schedule in paragraph (e)(8)(v) of this section. If requested by the Regional Administrator, this plan shall be revised and submitted to the Regional Administrator for approval within sixty (60) days of the request. The revised plan shall be implemented within sixty (60) days of the Regional Administrator's approval.
(ii) In the event that the owner or operator is unable to develop the plan required in paragraph (e)(8)(i) of this section due to technical difficulties, fails to submit the plan within sixty (60) days of the effective date of this FIP, or the Regional Administrator disapproves the plan, the owner or operator shall install and operate devices to measure the pressure drop across each scrubber module and the total flow of scrubbing liquid to the venturi section of each scrubber module. The data from these instruments shall be monitored and recorded electronically. A minimum of one reading every 15 minutes shall be used to calculate an hourly average which shall be recorded and stored for at least a five-year period. The owner or operator shall report in an electronic format either all hourly data, or one-hour averages deviating by more than 30 percent from the levels measured during the last particulate matter stack test that demonstrated compliance with the limit in this section. The owner or operator shall implement this requirement no later than one hundred eighty (180) days after the effective date of this FIP if it failed to submit the plan within sixty (60) days after the effective date of this FIP; or no later than 60 days after the Regional Administrator's disapproval of the plan.
(iii) The monitoring required under paragraphs (e)(8)(i) and (e)(8)(ii) of this section shall apply to each Unit at all times that the Unit is operating, except for monitoring malfunctions, associated repairs, and required quality assurance or control activities (including, as applicable, calibration checks and required zero and span adjustments). A monitoring malfunction is any sudden, infrequent, not reasonably preventable failure of the monitoring to provide valid data. Monitoring failures that are caused in part by poor maintenance or careless operation are not malfunctions.
(iv) The owner or operator may petition the Regional Administrator for an extension of the sixty (60) day deadline. Such extension shall be granted only if the owner or operator demonstrates to the satisfaction of the Regional Administrator that:
(A) The delay is due to technical infeasibility beyond the control of the owner or operator; and
(B) The requested extension, if granted, will allow the owner or operator to successfully complete the plan.
(v) The owner or operator shall submit to the Regional Administrator reports of the monitoring data required by this section semi-annually. The reports shall be postmarked within 30 days of the end of each calendar quarter.
(vi) The owner or operator shall develop and document a quality assurance program for the monitoring and recording instrumentation. This program shall be updated or improved as requested by the Regional Administrator.
(vii) In the event that a program for parameter monitoring on Units 1, 2, and 3 is approved pursuant to the Compliance Assurance Monitoring rule, 40 CFR Part 64, such program will supersede the provisions contained in paragraph (e)(8) of this section.
(f) Reporting and Recordkeeping Requirements. Unless otherwise stated all requests, reports, submittals, notifications, and other communications to the Regional Administrator required by this section shall be submitted, unless instructed otherwise, to the Director, Navajo Environmental Protection Agency, P.O. Box 339, Window Rock, Arizona 86515, (928) 871-7692, (928) 871-7996 (facsimile), and to the Director, Air Division, U.S. Environmental Protection Agency, Region IX, to the attention of Mail Code: AIR-5, at 75 Hawthorne Street, San Francisco, California 94105, (415) 972-3990, (415) 947-3579 (facsimile). For each unit subject to the emissions limitation in this section and upon completion of the installation of CEMS and COMS as required in this section, the owner or operator shall comply with the following requirements:
(1) For each emissions limit in this section, comply with the notification and recordkeeping requirements for CEMS compliance monitoring in 40 CFR 60.7(c) and (d). For Units 4 and 5, periods of excess opacity due to water droplets shall be reported in the summary report required by 40 CFR 60.7(d).
(2) For each day, provide the 365 day percent SO
(3) Furnish the Regional Administrator with reports describing the results of the annual particulate matter emissions tests postmarked within sixty (60) days of completing the tests. Each report shall include the following information:
(i) The test date;
(ii) The test method;
(iii) Identification of the coal burning equipment tested;
(iv) Values for stack pressure, temperature, moisture, and distribution of velocity heads;
(v) Average heat input;
(vi) Emissions data, identified by sample number, and expressed in pounds per MMBtu;
(vii) Arithmetic average of sample data expressed in pounds per MMBtu; and
(viii) A description of any variances from the test method.
(4) Excess Emissions Report. (i) For excess emissions (except in the case of saturated stack conditions), the owner or operator shall notify the Navajo Environmental Protection Agency Director and the U.S. Environmental Protection Agency Regional Administrator by telephone or in writing within one business day (initial notification). A complete written report of the incident shall be submitted to the Navajo Environmental Protection Agency Director and the U.S. Environmental Protection Agency Regional Administrator within ten (10) working days of the initial notification. This notification should be sent to the Director, Navajo Environmental Protection Agency, by mail to: P.O. Box 339, Window Rock, Arizona 86515, or by facsimile to: (928) 871-7996 (facsimile), and to the Regional Administrator, U.S. Environmental Protection Agency, by mail to the attention of Mail Code: AIR-5, at 75 Hawthorne Street, San Francisco, California 94105, by facsimile to: (415) 947-3579 (facsimile), or by e-mail to: [email protected]. The complete written report shall include:
(A) The name and title of the person reporting;
(B) The identity and location of the Plant and Unit(s) involved, and the emissions point(s), including bypass, from which the excess emissions occurred or are occurring;
(C) The time and duration or expected duration of the excess emissions;
(D) The magnitude of the excess emissions expressed in the units of the applicable emissions limitation and the operating data and calculations used in determining the magnitude of the excess emissions;
(E) The nature of the condition causing the excess emissions and the reasons why excess emissions occurred or are occurring;
(F) If the excess emissions were the result of a malfunction, the steps taken to remedy the malfunction and the steps taken or planned to prevent the recurrence of such malfunction;
(G) For an opacity exceedance, the 6-minute average opacity monitoring data greater than 20 percent for the 24 hours prior to and during the exceedance for Units 4 and 5; and
(H) The efforts taken or being taken to minimize the excess emissions and to repair or otherwise bring the Plant into compliance with the applicable emissions limit(s) or other requirements. For this reporting requirement, excess opacity due to saturated stack conditions is exempted.
(ii) If the period of excess emissions extends beyond the submittal of the written report, the owner or operator shall also notify the Regional Administrator in writing of the exact time and date when the excess emissions stopped. Compliance with the excess emissions notification provisions of this section shall not excuse or otherwise constitute a defense to any violations of this section or of any law or regulation which such excess emissions or malfunction may cause.
(g) Equipment Operations. At all times, including periods of startup, shutdown, and malfunction, the owner or operator shall, to the extent practicable, maintain and operate the Plant including associated air pollution control equipment in a manner consistent with good air pollution control practices for minimizing emissions. Determination of whether acceptable operating and maintenance procedures are being used will be based on information available to the Regional Administrator which may include, but is not limited to, monitoring results, opacity observations, review of operating and maintenance procedures, and inspection of the Plant. With regard to the operation of the baghouses on Units 4 and 5, placing the baghouses in service before coal fires are initiated will constitute compliance with this paragraph. (If the baghouse inlet temperature cannot achieve 185 degrees Fahrenheit using only gas fires, the owner or operator will not be expected to place baghouses in service before coal fires are initiated; however, the owner or operator will remain subject to the requirements of this paragraph.)
(h) Enforcement. (1) Notwithstanding any other provision in this implementation plan, any credible evidence or information relevant to whether the Plant would have been in compliance with applicable requirements if the appropriate performance or compliance test had been performed, can be used to establish whether or not the owner or operator has violated or is in violation of any standard in the plan.
(2) During periods of startup and shutdown the otherwise applicable emission limits or requirements for opacity and particulate matter shall not apply provided that:
(i) At all times the facility is operated in a manner consistent with good practice for minimizing emissions, and the owner or operator uses best efforts regarding planning, design, and operating procedures to meet the otherwise applicable emission limit;
(ii) The frequency and duration of operation in start-up or shutdown mode are minimized to the maximum extent practicable; and
(iii) The owner or operator's actions during start-up and shutdown periods are documented by properly signed, contemporaneous operating logs, or other relevant evidence.
(3) Emissions in excess of the level of the applicable emission limit or requirement that occur due to a malfunction shall constitute a violation of the applicable emission limit. However, it shall be an affirmative defense in an enforcement action seeking penalties if the owner or operator has met with all of the following conditions:
(i) The malfunction was the result of a sudden and unavoidable failure of process or air pollution control equipment or of a process to operate in a normal or usual manner;
(ii) The malfunction did not result from operator error or neglect, or from improper operation or maintenance procedures;
(iii) The excess emissions were not part of a recurring pattern indicative of inadequate design, operation, or maintenance;
(iv) Steps were taken in an expeditious fashion to correct conditions leading to the malfunction, and the amount and duration of the excess emissions caused by the malfunction were minimized to the maximum extent practicable;
(v) All possible steps were taken to minimize the impact of the excess emissions on ambient air quality;
(vi) All emissions monitoring systems were kept in operation if at all possible; and
(vii) The owner or operator's actions in response to the excess emissions were documented by properly signed, contemporaneous operating logs, or other relevant evidence.
(i) Regional Haze Best Available Retrofit Technology limits for this plant are in addition to the requirements of paragraphs (a) through (h) of this section. All definitions and testing and monitoring methods of this section apply to the limits in this paragraph (i) except as indicated in paragraphs (i)(1) through (4) of this section. The interim NO
(1) Particulate Matter from Units 4 and 5 shall be limited to 0.015 lb/MMBtu for each unit as measured by the average of three test runs with each run collecting a minimum of 60 dscf of sample gas and with a duration of at least 120 minutes. Sampling shall be performed according to 40 CFR Part 60 Appendices A-1 through A-3, Methods 1 through 4 and Method 5 or Method 5e. The averaging time for any other demonstration of the particulate matter compliance or exceedance shall be based on a 6-hour average. Particulate testing shall be performed annually as required by paragraph (e)(3) of this section. This test with 120 minute test runs may be substituted and used to demonstrate compliance with the particulate limits in paragraph (d)(2) of this section.
(2) Plant-wide nitrogen oxide emission limits.
(i) The plant-wide nitrogen oxide limit, expressed as nitrogen dioxide (NO
(ii) The interim NO
(iii) Schedule for add-on post-combustion NO
(A) Within 4 years of the effective date of this rule, FCPP shall have installed add-on post-combustion NO
(B) Within 5 years of the effective date of this rule, FCPP shall have installed add-on post-combustion NO
(iv) Testing and monitoring shall use the 40 CFR part 75 monitors and meet the 40 CFR part 75 quality assurance requirements. In addition to these 40 CFR part 75 requirements, relative accuracy test audits shall be performed for both the NO
(v) If a valid NO
(vi) Upon the effective date of the plant-wide NO
(3) In lieu of meeting the NO
(4) By January 1, 2013, the owner or operator shall submit a letter to the Regional Administrator updating EPA of the status of lease negotiations and regulatory approvals required to comply with paragraph (i)(3) of this section. By December 31, 2013, the owner or operator shall notify the Regional Administrator by letter whether it will comply with paragraph (i)(2) of this section or whether it will comply with paragraph (i)(3) of this section and shall submit a plan and time table for compliance with either paragraph (i)(2) or (3) of this section. The owner or operator shall amend and submit this amended plan to the Regional Administrator as changes occur.
(5) The owner or operator shall follow the requirements of 40 CFR part 71 for submitting an application for permit revision to update its Part 71 operating permit after it achieves compliance with paragraph (i)(2) or (3) of this section.
(j) Dust. Each owner or operator shall operate and maintain the existing dust suppression methods for controlling dust from the coal handling and ash handling and storage facilities. Within ninety (90) days after promulgation of this paragraph, the owner or operator shall develop a dust control plan and submit the plan to the Regional Administrator. The owner or operator shall comply with the plan once the plan is submitted to the Regional Administrator. The owner or operator shall amend the plan as requested or needed. The plan shall include a description of the dust suppression methods for controlling dust from the coal handling and storage facilities, ash handling, storage, and landfills, and road sweeping activities. Within 18 months of promulgation of this paragraph each owner or operator shall not emit dust with opacity greater than 20 percent from any crusher, grinding mill, screening operation, belt conveyor, or truck loading or unloading operation.
§ 49.5513 - [Reserved]
Implementation Plan for the Pechanga Band of Luiseño Mission Indians of the Pechanga Reservation
§ 49.5514 - EPA-approved Tribal rules and plans.
(a) Purpose and scope. This section contains the approved implementation plan for the Pechanga Band of Luiseño Mission Indians of the Pechanga Reservation dated May 2014. The plan consists of a redesignation request, a demonstration of maintenance of the 1997 8-hour ozone national ambient air quality standard, and related commitments to continue monitoring and to implement contingency provisions in the event of a monitored violation of the standard.
(b)-(c) [Reserved]
(d) EPA-approved nonregulatory provisions and quasi-regulatory measures.
EPA-Approved Nonregulatory Provisions and Quasi-Regulatory Measures for the Pechanga Band of Luiseño Mission Indians of the Pechanga Reservation
Name of nonregulatory or quasi-regulatory TIP provision | Tribal submittal date | EPA approval date | Explanation | Ozone Redesignation Request and Maintenance Plan for Pechanga Band of Luiseño Mission Indians of the Pechanga Reservation Nonattainment Area (May 2014) | November 4, 2014 | 80 FR 18130, April 3, 2015 | Tribal redesignation request and maintenance plan for the 1997 8-hour ozone standard. |
---|
Implementation Plan for the Salt River Pima-Maricopa Indian Community
§ 49.5515 - Federal implementation plan for Tri-Cities landfill, Salt River Pima-Maricopa Indian Community.
(a) Applicability. This section applies to the owner or operator of the project located on the Reservation of the Salt River Pima Maricopa Indian Community (SRPMIC) in Arizona, including any new owner or operator in the event of a change in ownership of the project.
(b) Definitions. The following definitions apply to this section. Except as specifically defined herein, terms used in this section retain the meaning accorded them under the Clean Air Act.
Actual emissions means the actual rate of emissions of a pollutant from an emissions unit as determined in paragraphs (1)-(3) of this definition:
(1) In general, actual emissions as of a particular date shall equal the average rate, in tons per year, at which the unit actually emitted the pollutant during a two-year period which precedes the particular date and which is representative of normal source operation. EPA shall allow the use of a different time period upon a determination that it is more representative of normal source operation. Actual emissions shall be calculated using the unit's actual operating hours, production rates, and types of materials processed, stored, or combusted during the selected time period.
(2) EPA may presume that the source-specific allowable emissions for the unit are equivalent to the actual emissions of the unit.
(3) For any emissions unit which has not begun normal operations on the particular date, actual emissions shall equal the potential to emit of the unit on that date.
Begin actual construction means, in general, initiation of physical on-site construction activities on an emissions unit which are of a permanent nature. Such activities include, but are not limited to, installation of building supports and foundations, laying of underground pipework, and construction of permanent storage structures. With respect to a change in method of operating this term refers to those on-site activities other than preparatory activities which mark the initiation of the change.
Building, structure, facility, or installation means all of the pollutant-emitting activities which belong to the same industrial grouping, are located on one or more contiguous or adjacent properties, and are under the control of the same person (or persons under common control) except the activities of any vessel. Pollutant-emitting activities shall be considered as part of the same industrial grouping if they belong to the same Major Group (i.e., which have the same two-digit code) as described in the Standard Industrial Classification Manual, 1972, as amended by the 1977 Supplement (U.S. Government Printing Office stock numbers 4101-0065 and 003-005-00176-0, respectively).
Commence as applied to construction of a major stationary source or major modification means that the owner or operator has all necessary preconstruction approvals or permits and either has: (1) Begun, or caused to begin, a continuous program of actual on-site construction of the source, to be completed within a reasonable time; or
(2) Entered into binding agreements or contractual obligations, which cannot be cancelled or modified without substantial loss to the owner or operator, to undertake a program of actual construction of the source to be completed within a reasonable time.
Construction means any physical change or change in the method of operation (including fabrication, erection, installation, demolition, or modification of an emissions unit) which would result in a change in actual emissions.
EPA means United States Environmental Protection Agency, Region 9.
Fugitive emissions means those emissions which could not reasonably pass through a stack, chimney, vent, or other functionally equivalent opening.
Lowest achievable emission rate means the more stringent rate of emissions based on the following:
(1) The most stringent emissions limitation which is contained in any State, Tribal, or federal implementation plan for such class or category of stationary source, unless the owner or operator of the project demonstrates that such limitations are not achievable; or
(2) The most stringent emissions limitation which is achieved in practice by such class or category of stationary sources. This limitation, when applied to a modification, means the lowest achievable emissions rate for the new or modified emissions units within a stationary source. In no event shall the application of the term permit a proposed new or modified stationary source to emit any pollutant in excess of the amount allowable under an applicable new source standard of performance.
Major stationary source means a stationary source of air pollutants which emits, or has the potential to emit, 100 tons per year or more of any pollutant subject to regulation under the Act. The fugitive emissions of a stationary source shall not be included in determining for any of the purposes of this project whether it is a major stationary source.
Potential to emit means the maximum capacity of a stationary source to emit a pollutant under its physical and operational design. Any physical or operational limitation on the capacity of the source to emit a pollutant, including air pollution control equipment and restrictions on hours of operation or on the type or amount of material combusted, stored, or processed, shall be treated as part of its design only if the limitation or the effect it would have on emissions is federally enforceable. Secondary emissions do not count in determining the potential to emit of a stationary source.
Project means the construction of electricity-generating engines owned and operated by the Salt River Project at the Tri-Cities landfill, which are fueled by collected landfill gas.
Secondary emissions means emissions which would occur as a result of the construction or operation of a major stationary source, but do not come from the major stationary source itself. For the purpose of this section, secondary emissions must be specific, well defined, quantifiable, and impact the same general area as the stationary source which causes the secondary emissions. Secondary emissions include emissions from any offsite support facility which would not be constructed or increase its emissions except as a result of the construction of operation of the major stationary source. Secondary emissions do not include any emissions which come directly from a mobile source such as emissions from the tailpipe of a motor vehicle, from a train, or from a vessel.
Stationary source means any building, structure, facility, or installation which emits or may emit any air pollutant subject to regulation under the Clean Air Act.
(c) Requirement to submit an application. The owner or operator of the project shall submit an application for a permit to construct to EPA which contains all information necessary to perform any analysis or make any determination as required by this Federal Implementation Plan.
(d) Source obligations. (1) The owner or operator of the project shall not begin actual construction on the project without obtaining a nonattainment New Source Review permit regulating emissions of air pollutants. The EPA Region 9 Regional Administrator has the authority to issue such a permit. Any permit issued by EPA shall ensure that the project meets the following requirements:
(i) By the time the project is to commence operation, the owner or operator of the project must have obtained sufficient reductions in actual emissions from existing facilities within the same nonattainment area which satisfy the requirements of section 173 of the Clean Air Act, to offset the potential to emit of the project;
(ii) The owner or operator of the project must comply with the lowest achievable emissions rate;
(iii) The owner or operator of the project must demonstrate that all major stationary sources owned or operated by such person (or by any entity controlling, controlled by, or under common control with such person) located on the reservation of the SRPMIC are subject to emission limitations and are in compliance, or on a schedule for compliance, with all applicable emission limitations and standards under the Act; and
(iv) The owner or operator of the project has provided an analysis of alternative sites, sizes, production processes, and environmental control techniques for the proposed source which demonstrates that benefits of the proposed source significantly outweigh the environmental and social costs imposed as a result of its location or construction.
(2) If the owner or operator constructs or operates the project not in accordance with the application submitted pursuant to this section or with the terms of any approval to construct, or if the owner or operator subject to this section commences construction after January 24 , 2000 without applying for and receiving approval under this section, then the owner or operator shall be subject to appropriate enforcement action.
(3) Approval to construct shall become invalid if construction is not commenced within 18 months after receipt of such approval, if construction is discontinued for a period of 18 months or more, or if construction is not completed within a reasonable time. The Administrator may extend the 18-month period upon a satisfactory showing that an extension is justified.
(4) Approval to construct shall not relieve any owner or operator of the responsibility to comply fully with applicable provisions of the Federal implementation plan and any other requirements under Tribal or Federal law.
(e) Public participation. (1) When issuing a permit for the project, the EPA Region 9 Regional Administrator shall follow the procedures for decision making for PSD permits contained in 40 CFR part 124, including the requirements for public notice, consideration of and response to public comment, and the opportunity for public hearing.
(2) Within 30 days after the EPA Region 9 Regional Administrator has issued a final permit decision, any person who filed comments on the draft permit or participated in the public hearing, if one has been held, may petition the Environmental Appeals Board to review any condition of the permit. Review of the permit decision will be governed by the regulations for review of PSD permits contained in 40 CFR part 124.