§ 111.55-1 - General.

(a) Each switch must meet Article 404 of NFPA 70 (incorporated by reference; see Ҥ 110.10-1 of this subchapter).

(b) Each switch that is in the weather must be in a watertight enclosure and be externally operable.

[CGD 74-125A, 47 FR 15236, Apr. 8, 1982, as amended by USCG-2003-16630, 73 FR 65198, Oct. 31, 2008; USCG-2020-0075, 88 FR 16363, Mar. 16, 2023]

§ 111.55-3 - Circuit connections.

The load side of each circuit must be connected to the fuse end of a fused-switch or to the coil end of a circuit breaker, except a generator which is connected to either end of a circuit breaker.