§ 112.35-1 - General.

This subpart contains requirements applicable to emergency power installations having a manually controlled storage battery, diesel engine, or gas turbine driven generator as the sole emergency power source.

§ 112.35-3 - Normal source for emergency loads.

The normal source for emergency loads must be the ship's service generating plant.

§ 112.35-5 - Manually started emergency systems.

Manually started emergency lighting and power systems must be activated by one manual operation, such as the manual operation of a switch from an “off” to an “on” position, to cause the emergency system to supply its connected loads.

§ 112.35-7 - Activating means.

The activating means must be in the navigating bridge or in a location where the means can be controlled by the chief engineer.