Collapse to view only § 98.305 - Procedures for estimating missing data.
- § 98.300 - Definition of the source category.
- § 98.301 - Reporting threshold.
- § 98.302 - GHGs to report.
- § 98.303 - Calculating GHG emissions.
- § 98.304 - Monitoring and QA/QC requirements.
- § 98.305 - Procedures for estimating missing data.
- § 98.306 -
- § 98.307 - Records that must be retained.
- § 98.308 - Definitions.
§ 98.300 - Definition of the source category.
(a) The electrical transmission and distribution equipment use source category consists of all electric transmission and distribution equipment and servicing inventory insulated with or containing fluorinated GHGs, including but not limited to sulfur hexafluoride (SF
(1) Gas-insulated substations.
(2) Circuit breakers.
(3) Switchgear, including closed-pressure and hermetically sealed-pressure switchgear and gas-insulated lines containing fluorinated GHGs, including but not limited to SF
(4) Gas containers such as pressurized cylinders.
(5) Gas carts.
(6) Electric power transformers.
(7) Other containers of fluorinated GHG, including but not limited to SF
(b) [Reserved]
§ 98.301 - Reporting threshold.
(a) You must report GHG emissions under this subpart if you are an electric power system as defined in § 98.308 and your facility meets the requirements of § 98.2(a)(1). To calculate total annual GHG emissions for comparison to the 25,000 metric ton CO

(b) A facility other than an electric power system that is subject to this part because of emissions from any other source category listed in table A-3 or A-4 to subpart A of this part is not required to report emissions under subpart DD of this part unless the total estimated emissions of fluorinated GHGs that are components of reportable insulating gases, as calculated in equation DD-2 to this section, equals or exceeds 25,000 tons CO

§ 98.302 - GHGs to report.
You must report emissions of each fluorinated GHG, including but not limited to SF

§ 98.303 - Calculating GHG emissions.
(a) Calculating GHG emissions. Calculate the annual emissions of each fluorinated GHG that is a component of any reportable insulating gas using the mass-balance approach in equation DD-4 to this section:

(b) Nameplate capacity adjustments. Users of closed-pressure electrical equipment with a voltage capacity greater than 38 kV may measure and adjust the nameplate capacity value specified by the equipment manufacturer on the nameplate attached to that equipment, or within the equipment manufacturer's official product specifications, by following the requirements in paragraphs (b)(1) through (10) of this section. Users of other electrical equipment are not permitted to adjust the nameplate capacity value of the other equipment.
(1) If you elect to measure the nameplate capacity value(s) of one or more pieces of electrical equipment with a voltage capacity greater than 38 kV, you must measure the nameplate capacity values of all the electrical equipment in your facility that has a voltage capacity greater than 38 kV and that is installed or retired in that reporting year and in subsequent reporting years.
(2) You must adopt the measured nameplate capacity value for any piece of equipment for which the absolute value of the difference between the measured nameplate capacity value and the nameplate capacity value most recently specified by the manufacturer equals or exceeds two percent of the nameplate capacity value most recently specified by the manufacturer.
(3) You may adopt the measured nameplate capacity value for equipment for which the absolute value of the difference between the measured nameplate capacity value and the nameplate capacity value most recently specified by the manufacturer is less than two percent of the nameplate capacity value most recently specified by the manufacturer, but if you elect to adopt the measured nameplate capacity for that equipment, then you must adopt the measured nameplate capacity value for all of the equipment for which the difference between the measured nameplate capacity value and the nameplate capacity value most recently specified by the manufacturer is less than two percent of the nameplate capacity value most recently specified by the manufacturer. This applies in the reporting year in which you first adopt the measured nameplate capacity for the equipment and in subsequent reporting years.
(4) Users of electrical equipment measuring the nameplate capacity of any new electrical equipment must:
(i) Record the amount of insulating gas in the equipment at the time the equipment was acquired (pounds), either per information provided by the manufacturer, or by transferring insulating gas from the equipment to a gas container and measuring the amount of insulating gas transferred. The equipment user is responsible for ensuring the gas is accounted for consistent with the methodologies specified in paragraphs (b)(4)(ii) through (iii) and (b)(5) of this section. If no insulating gas was in the device when it was acquired, record this value as zero.
(ii) If insulating gas is added to the equipment subsequent to the acquisition of the equipment to energize it the first time, transfer the insulating gas to the equipment to reach the temperature-compensated design operating pressure per manufacturer specifications. Follow the manufacturer-specified procedure to ensure that the measured temperature accurately reflects the temperature of the insulating gas, e.g., by measuring the insulating gas pressure and vessel temperature after allowing appropriate time for the temperature of the transferred gas to equilibrate with the vessel temperature. Measure and calculate the total amount of reportable insulating gas added to the device using one of the methods specified in paragraphs (b)(4)(ii)(A) and (B) of this section.
(A) To determine the amount of reportable insulating gas transferred to the electrical equipment, weigh the gas container being used to fill the device prior to, and after, the addition of the reportable insulating gas to the electrical equipment, and subtract the second value (after-transfer gas container weight) from the first value (prior-to-transfer gas container weight). Account for any gas contained in hoses before and after the transfer.
(B) Connect a mass flow meter between the electrical equipment and a gas cart. Transfer gas to the equipment to reach the temperature-compensated design operating pressure per manufacturer specifications. During gas transfer, you must keep the mass flow rate within the range specified by the mass flow meter manufacturer to assure an accurate and precise mass flow meter reading. Close the connection to the GIE from the mass flow meter hose and ensure that the gas trapped in the filling hose returns through the mass flow meter. Calculate the amount of gas transferred from the mass reading on the mass flow meter.
(iii) Sum the results of paragraphs (b)(4)(i) and (ii) to obtain the measured nameplate capacity for the new equipment.
(5) Electrical equipment users measuring the nameplate capacity of any retiring electrical equipment must:
(i) Measure and record the initial system pressure and vessel temperature prior to removing any insulating gas.
(ii) Compare the initial system pressure and temperature to the equipment manufacturer's temperature/pressure curve for that equipment and insulating gas.
(iii) If the temperature-compensated initial system pressure of the electrical equipment does not match the temperature-compensated design operating pressure specified by the equipment manufacturer, you may either:
(A) Add or remove insulating gas to/from the electrical equipment until the manufacturer-specified value is reached, or
(B) If the temperature-compensated initial system pressure of the electrical equipment is no higher than the temperature-compensated design operating pressure specified by the manufacturer and no lower than five pounds per square inch (5 psi) less than the temperature-compensated design operating pressure specified by the manufacturer, use equation DD-5 to this section to calculate the nameplate capacity based on the mass recorded under paragraph (b)(5)(vi) of this section.
(iv) Weigh the gas container being used to receive the gas and record this value.
(v) Recover insulating gas from the electrical equipment until five minutes after the pressure in the electrical equipment reaches a pressure of at most five pounds per square inch absolute (5 psia).
(vi) Record the amount of insulating gas recovered (pounds) by weighing the gas container that received the gas and subtracting the weight recorded pursuant to paragraph (b)(5)(iv)(B) of this section from this value. Account for any gas contained in hoses before and after the transfer. The amount of gas recovered shall be the measured nameplate capacity for the electrical equipment unless the final temperature-compensated pressure of the electrical equipment exceeds 0.068 psia (3.5 Torr) or the electrical equipment user is calculating the nameplate capacity pursuant to paragraph (b)(5)(iii)(B) of this section, in which cases the measured nameplate capacity shall be the result of equation DD-5 to this section.
(vii) If you are calculating the nameplate capacity pursuant to paragraph (b)(5)(iii)(B) of this section, use equation DD-5 to this section to do so.

(viii) Record the final system pressure and vessel temperature.
(6) Instead of measuring the nameplate capacity of electrical equipment when it is retired, users may measure the nameplate capacity of electrical equipment during maintenance activities that require opening the gas compartment, but they must follow the procedures set forth in paragraph (b)(5) of this section.
(7) If the electrical equipment will remain energized, and the electrical equipment user is adopting the user-measured nameplate capacity, the electrical equipment user must affix a revised nameplate capacity label, showing the revised nameplate value and the year the nameplate capacity adjustment process was performed, to the device by the end of the calendar year in which the process was completed. The manufacturer's previous nameplate capacity label must remain visible after the revised nameplate capacity label is affixed to the device.
(8) For each piece of electrical equipment whose nameplate capacity was adjusted during the reporting year, the revised nameplate capacity value must be used in all provisions wherein the nameplate capacity is required to be recorded, reported, or used in a calculation in this subpart unless otherwise specified herein.
(9) The nameplate capacity of a piece of electrical equipment may only be adjusted more than once if the physical capacity of the device has changed (e.g., replacement of bushings) after the initial adjustment was performed, in which case the equipment user must adjust the nameplate capacity pursuant to the provisions of this paragraph (b).
(10) Measuring devices used to measure the nameplate capacity of electrical equipment under this paragraph (b) must meet the following accuracy and precision requirements:
(i) Flow meters must be certified by the manufacturer to be accurate and precise to within one percent of the largest value that the flow meter can, according to the manufacturer's specifications, accurately record.
(ii) Pressure gauges must be certified by the manufacturer to be accurate and precise to within 0.5% of the largest value that the gauge can, according to the manufacturer's specifications, accurately record.
(iii) Temperature gauges must be certified by the manufacturer to be accurate and precise to within ±1.0 °F.
(iv) Scales must be certified by the manufacturer to be accurate and precise to within one percent of the true weight.
§ 98.304 - Monitoring and QA/QC requirements.
(a) [Reserved]
(b) You must adhere to the following QA/QC methods for reviewing the completeness and accuracy of reporting:
(1) Review inputs to equation DD-4 to § 98.303 to ensure inputs and outputs to the company's system are included.
(2) Do not enter negative inputs and confirm that negative emissions are not calculated. However, the Decrease in fluorinated GHG Inventory and the Net Increase in Total Nameplate Capacity may be calculated as negative numbers.
(3) Ensure that beginning-of-year inventory matches end-of-year inventory from the previous year.
(4) Ensure that in addition to fluorinated GHG purchased from bulk gas distributors, fluorinated GHG purchased from Original Equipment Manufacturers (OEM) and fluorinated GHG returned to the facility from off-site recycling are also accounted for among the total additions.
(c) Ensure the following QA/QC methods are employed throughout the year:
(1) Ensure that cylinders returned to the gas supplier are consistently weighed on a scale that is certified to be accurate and precise to within 2 pounds of true weight and is periodically recalibrated per the manufacturer's specifications. Either measure residual gas (the amount of gas remaining in returned cylinders) or have the gas supplier measure it. If the gas supplier weighs the residual gas, obtain from the gas supplier a detailed monthly accounting, within ±2 pounds, of residual gas amounts in the cylinders returned to the gas supplier.
(2) Ensure that cylinders weighed for the beginning and end of year inventory measurements are weighed on a scale that is certified to be accurate and precise to within 2 pounds of true weight and is periodically recalibrated per the manufacturer's specifications. All scales used to measure quantities that are to be reported under § 98.306 must be calibrated using calibration procedures specified by the scale manufacturer. Calibration must be performed prior to the first reporting year. After the initial calibration, recalibration must be performed at the minimum frequency specified by the manufacturer.
(3) Ensure all substations have provided information to the manager compiling the emissions report (if it is not already handled through an electronic inventory system).
(d) GHG Monitoring Plans, as described in § 98.3(g)(5), must be completed by April 1, 2011.
§ 98.305 - Procedures for estimating missing data.
A complete record of all measured parameters used in the GHG emissions calculations is required. Replace missing data, if needed, based on data from equipment with a similar nameplate capacity for fluorinated GHGs, and from similar equipment repair, replacement, and maintenance operations.
§ 98.306 -
In addition to the information required by § 98.3(c), each annual report must contain the following information for each electric power system, by chemical:
(a) Nameplate capacity of equipment (pounds) containing each insulating gas:
(1) Existing at the beginning of the year (excluding hermetically sealed-pressure switchgear).
(2) New hermetically sealed-pressure switchgear during the year.
(3) New equipment other than hermetically sealed-pressure switchgear during the year.
(4) Retired hermetically sealed-pressure switchgear during the year.
(5) Retired equipment other than hermetically sealed-pressure switchgear during the year.
(b) Transmission miles (length of lines carrying voltages above 35 kilovolts).
(c) Distribution miles (length of lines carrying voltages at or below 35 kilovolts).
(d) Pounds of each reportable insulating gas stored in containers, but not in energized equipment, at the beginning of the year.
(e) Pounds of each reportable insulating gas stored in containers, but not in energized equipment, at the end of the year.
(f) Pounds of each reportable insulating gas purchased or otherwise acquired in bulk from chemical producers, chemical distributors, or other entities.
(g) Pounds of each reportable insulating gas purchased or otherwise acquired from equipment manufacturers, equipment distributors, or other entities with or inside equipment, including hermetically sealed-pressure switchgear, while the equipment was not in use.
(h) Pounds of each reportable insulating gas returned to facility after off-site recycling.
(i) Pounds of each reportable insulating gas acquired inside equipment, except hermetically sealed-pressure switchgear, that was transferred while the equipment was in use, e.g., through acquisition of all or part of another electric power system.
(j) Pounds of each reportable insulating gas returned to suppliers.
(k) Pounds of each reportable insulating gas that was sold or transferred to other entities in bulk.
(l) Pounds of each reportable insulating gas sent off-site for recycling.
(m) Pounds of each reportable insulating gas sent off-site for destruction.
(n) Pounds of each reportable insulating gas contained in equipment, including hermetically sealed-pressure switchgear, that was sold or transferred to other entities while the equipment was not in use.
(o) Pounds of each reportable insulating gas disbursed inside equipment, except hermetically sealed-pressure switchgear, that was transferred while the equipment was in use, e.g., through sale of all or part of the electric power system to another electric power system.
(p) State(s) or territory in which the facility lies.
(q) The number of reportable-insulating-gas-containing pieces of equipment in each of the following equipment categories:
(1) New hermetically sealed-pressure switchgear during the year.
(2) New equipment other than hermetically sealed-pressure switchgear during the year.
(3) Retired hermetically sealed-pressure switchgear during the year.
(4) Retired equipment other than hermetically sealed-pressure switchgear during the year.
(r) The total of the nameplate capacity values most recently assigned by the electrical equipment manufacturer(s) to each of the following groups of equipment:
(1) All new equipment whose nameplate capacity values were measured by the user under this subpart and for which the user adopted the user-measured nameplate capacity value during the year.
(2) All retiring equipment whose nameplate capacity values were measured by the user under this subpart and for which the user adopted the user-measured nameplate capacity value during the year.
(s) The total of the nameplate capacity values measured by the electrical equipment user for each of the following groups of equipment:
(1) All new equipment whose nameplate capacity values were measured by the user under this subpart and for which the user adopted the user-measured nameplate capacity value during the year.
(2) All retiring equipment whose nameplate capacity values were measured by the user under this subpart and for which the user adopted the user-measured nameplate capacity value during the year.
(t) For each reportable insulating gas reported in paragraphs (a), (d) through (o), and (q) of this section, an ID number or other appropriate descriptor that is unique to that reportable insulating gas.
(u) For each ID number or descriptor reported in paragraph (t) of this section for each unique insulating gas, the name (as required in § 98.3(c)(4)(iii)(G)(1)) and weight percent of each fluorinated gas in the insulating gas.
§ 98.307 - Records that must be retained.
(a) In addition to the information required by § 98.3(g), you must retain records of the information reported and listed in § 98.306.
(b) For each piece of electrical equipment whose nameplate capacity is measured by the equipment user, retain records of the following:
(1) Equipment manufacturer name.
(2) Year equipment was manufactured. If the date year the equipment was manufactured cannot be determined, report a best estimate of the year of manufacture and record how the estimated year was determined.
(3) Manufacturer serial number. For any piece of equipment whose serial number is unknown (e.g., the serial number does not exist or is not visible), another unique identifier must be recorded as the manufacturer serial number. The electrical equipment user must retain documentation that allows for each electrical equipment to be readily identifiable.
(4) Equipment type (i.e., closed-pressure vs. hermetically sealed-pressure).
(5) Equipment voltage capacity (in kilovolts).
(6) The name and GWP of each insulating gas used.
(7) Nameplate capacity value (pounds), as specified by the equipment manufacturer. The value must reflect the latest value specified by the manufacturer during the reporting year.
(8) Nameplate capacity value (pounds) measured by the equipment user.
(9) The date the nameplate capacity measurement process was completed.
(10) The measurements and calculations used to calculate the value in paragraph (b)(8) of this section.
(11) The temperature-pressure curve and/or other information used to derive the initial and final temperature-adjusted pressures of the equipment.
(12) Whether or not the nameplate capacity value in paragraph (b)(8) of this section has been adopted for the piece of electrical equipment.
§ 98.308 - Definitions.
Except as specified in this section, all terms used in this subpart have the same meaning given in the Clean Air Act and subpart A of this part.
Facility, with respect to an electric power system, means the electric power system as set out in this definition. An electric power system is comprised of all electric transmission and distribution equipment insulated with or containing fluorinated GHGs that is linked through electric power transmission or distribution lines and functions as an integrated unit, that is owned, serviced, or maintained by a single electric power transmission or distribution entity (or multiple entities with a common owner), and that is located between:
(1) The point(s) at which electric energy is obtained from an electricity generating unit or a different electric power transmission or distribution entity that does not have a common owner; and
(2) The point(s) at which any customer or another electric power transmission or distribution entity that does not have a common owner receives the electric energy. The facility also includes servicing inventory for such equipment that contains fluorinated GHGs.
Electric power transmission or distribution entity means any entity that transmits, distributes, or supplies electricity to a consumer or other user, including any company, electric cooperative, public electric supply corporation, a similar Federal department (including the Bureau of Reclamation or the Corps of Engineers), a municipally owned electric department offering service to the public, an electric public utility district, or a jointly owned electric supply project.
Energized, for the purposes of this subpart, means connected through busbars or cables to an electrical power system or fully-charged, ready for service, and being prepared for connection to the electrical power system. Energized equipment does not include spare gas insulated equipment (including hermetically-sealed pressure switchgear) in storage that has been acquired by the facility, and is intended for use by the facility, but that is not being used or prepared for connection to the electrical power system.
Insulating gas, for the purposes of this subpart, means any fluorinated GHG or fluorinated GHG mixture, including but not limited to SF
New equipment, for the purposes of this subpart, means either any gas insulated equipment, including hermetically-sealed pressure switchgear, that is not energized at the beginning of the reporting year but is energized at the end of the reporting year, or any gas insulated equipment other than hermetically-sealed pressure switchgear that has been transferred while in use, meaning it has been added to the facility's inventory without being taken out of active service (e.g., when the equipment is sold to or acquired by the facility while remaining in place and continuing operation).
Operator, for the purposes of this subpart, means any person who operates or supervises a facility, excluding a person whose sole responsibility is to ensure reliability, balance load or otherwise address electricity flow.
Reportable insulating gas, for purposes of this subpart, means an insulating gas whose weighted average GWP, as calculated in equation DD-3 to § 98.302, is greater than one. A fluorinated GHG that makes up either part or all of a reportable insulating gas is considered to be a component of the reportable insulating gas.
Retired equipment, for the purposes of this subpart, means either any gas insulated equipment including hermetically-sealed pressure switchgear, that is energized at the beginning of the reporting year but is not energized at the end of the reporting year, or any gas insulated equipment other than hermetically-sealed pressure switchgear that has been transferred while in use, meaning it has been removed from the facility's inventory without being taken out of active service (e.g., when the equipment is acquired by a new facility while remaining in place and continuing operation).