§ 3285.303 - Piers.

(a) General. The piers used must be capable of transmitting the vertical live and dead loads to the footings or foundation.

(b) Acceptable piers—materials specification. (1) Piers are permitted to be concrete blocks; pressure-treated wood with a water borne preservative, in accordance with AWPA Standard U1-04 (incorporated by reference, see § 3285.4) for Use Category 4B ground contact applications; or adjustable metal or concrete piers.

(2) Manufactured piers must be listed or labeled for the required vertical load capacity, and, where required by design, for the appropriate horizontal load capacity.

(c) Design requirements. (1) Load-bearing capacity. The load bearing capacity for each pier must be designed to include consideration for the dimensions of the home, the design dead and live loads, the spacing of the piers, and the way the piers are used to support the home.

(2) Center beam/mating wall support must be required for multi-section homes and designs must be consistent with Tables 2 and 3 to § 3285.303 and Figures A, B, and C to § 3285.310.

(d) Pier loads. (1) Design support configurations for the pier loads, pier spacing, and roof live loads must be in accordance with Tables 1, 2, and 3 to § 3285.303 and the MHCSS. Other pier designs are permitted in accordance with the provisions of this subpart.

(2) Manufactured piers must be rated at least to the loads required to safely support the dead and live loads, as required by § 3285.301, and the installation instructions for those piers must be consistent with Tables 1, 2, and 3 to this section.

Table 1 to § 3285.303—Frame Blocking Only/Perimeter Support Not Required Except at Openings

Pier spacing Roof live load (psf) Location Load (lbs.) 20Frame2,900 4 ft. 0 in.30Frame3,300 40Frame3,600 20Frame4,200 6 ft. 0 in.30Frame4,700 40Frame5,200 20Frame5,500 8 ft. 0 in.30Frame6,200 40Frame6,900 20Frame6,800 10 ft. 0 in.30Frame7,600 40Frame8,500
Notes:

1. See Table to § 3285.312 for cast-in-place footing design by using the noted loads.

2. Table 1 is based on the following design assumptions: maximum 16 ft. nominal section width (15 ft. actual width), 12” eave, 10” I-beam size, 300 lbs. pier dead load, 10 psf roof dead load, 6 psf floor dead load, 35 plf wall dead load, and 10 plf chassis dead load.

3. Interpolation for other pier spacing is permitted.

4. The pier spacing and loads shown in the above table do not consider flood or seismic loads and are not intended for use in flood or seismic hazard areas. In those areas, the foundation support system is to be designed by a professional engineer or architect.

5. See Table to § 3285.312 for sizing of footings.

Table 2 to § 3285.303—Frame Plus Perimeter Blocking/Perimeter Blocking Required

Maximum pier spacing Roof live load(psf) Location Load (lbs.) Frame1,400 4 ft. 0 in.20Perimeter1,900 Mating3,200 Frame1,400 4 ft. 0 in.30Perimeter2,300 Mating3,800 Frame1,400 4 ft. 0 in.40Perimeter2,600 Mating4,400 Frame1,900 6 ft. 0 in.20Perimeter2,700 Mating4,700 Frame1,900 6 ft. 0 in.30Perimeter3,200 Mating5,600 Frame1,900 6 ft. 0 in.40Perimeter3,700 Mating6,500 Frame2,400 8 ft. 0 in.20Perimeter3,500 Mating6,100 Frame2,400 8 ft. 0 in.30Perimeter4,200 Mating7,300 Frame2,400 8 ft. 0 in.40Perimeter4,800 Mating8,500 Frame2,900 10 ft. 0 in.20Perimeter4,300 Mating7,600 Frame2,900 10 ft. 0 in.30Perimeter5,100 Mating9,100 Frame2,900 10 ft. 0 in.40Perimeter6,000 Mating10,600
Notes:

1. See Table to § 3285.312 for cast-in-place footing design by using the noted loads.

2. Mating wall perimeter piers and footings only required under full height mating walls supporting roof loads. Refer to Figures A and B to § 3285.310.

3. Table 2 is based on the following design assumptions: maximum 16 ft. nominal section width (15 ft. actual width), 12” eave, 10” I-beam size, 300 lbs. pier dead load, 10 psf roof dead load, 6 psf floor dead load, 35 plf wall dead load, and 10 plf chassis dead load.

4. Interpolation for other pier spacing is permitted.

5. The pier spacing and loads shown in the above table do not consider flood or seismic loads and are not intended for use in flood or seismic hazard areas. In those areas, the foundation support system is to be designed by a professional engineer or architect.

6. See Table to § 3285.312 for sizing of footings.

Table 3 to § 3285.303—Ridge Beam Span Footing Capacity

Mating wall opening (ft) Roof live load (psf) Pier and footing load (lbs.) 201,200 5301,600 401,900 202,300 10303,100 403,800 203,500 15304,700 405,800 204,700 20306,200 407,500 205,800 25307,800 409,700 207,000 30309,300 4011,600 208,100 353010,900 4013,600
Notes:

1. See Table to § 3285.312 for cast-in-place footing design by using the noted loads.

2. Table 3 is based on the following design assumptions: maximum 16 ft. nominal section width (15 ft. actual width), 10″ I-beam size, 300 lbs. pier dead load, 10 psf roof dead load, 6 psf floor dead load, 35 plf wall dead load, and 10 plf chassis dead load.

3. Loads listed are maximum column loads for each section of the manufactured home.

4. Interpolation for maximum allowable pier and column loads is permitted for mate-line openings between those shown in the table.

5. The pier spacing and loads shown in the above table do not consider flood or seismic loads and are not intended for use in flood or seismic hazard areas. In those areas, the foundation support system must be designed by a professional engineer or registered architect.

6. See Table to § 3285.312 for sizing of footings.