§ 18.24 -

Minimum clearances between uninsulated electrical conductor surfaces, or between uninsulated conductor surfaces and grounded metal surfaces, within the enclosure shall be as follows:

Minimum Clearances Between Uninsulated Surfaces

Phase-to-Phase Voltage (rms) Clearances (inches) Phase-to-Phase Phase-to-Ground or Control Circuit 0 to 2500.250.25 251 to 6000.280.25 601 to 10000.610.25 1001 to 24001.40.6 2401 to 41603.01.4