- Table 3 to Subpart HHH of Part 62—Operating Parameters To Be Monitored and Minimum Measurement and Recording Frequencies

Operating
parameters
to be
monitored
Minimum frequency HMIWI Data measurement Data recording HMIWI with combustion control only HMIWI with dry scrubber followed by FF HMIWI with wet scrubber HMIWI with dry scrubber followed by FF and wet scrubber HMIWI with SNCR system Maximum operating parameters: Maximum charge rateOnce per chargeOnce per charge✓✓✓✓✓ Maximum FF inlet temperatureContinuousOnce per minute✓✓ Maximum flue gas temperatureContinuousOnce per minute✓✓ Minimum operating parameters: Minimum secondary chamber temperatureContinuousOnce per minute✓✓✓✓✓ Minimum dioxin/furan sorbent flow rateHourlyOnce per hour✓✓ Minimum HCl sorbent flow rateHourlyOnce per hour✓✓ Minimum mercury (Hg) sorbent flow rateHourlyOnce per hour✓✓ Minimum pressure drop across the wet scrubber or minimum horsepower or amperage to wet scrubberContinuousOnce per minute✓✓ Minimum scrubber liquor flow rateContinuousOnce per minute✓✓ Minimum scrubber liquor pHContinuousOnce per minute✓✓ Minimum reagent flow rateHourlyOnce per hour✓