§ 52.45 - What are the requirements of the Federal Implementation Plans (FIPs) relating to ozone season emissions of nitrogen oxides from the Basic Chemical Manufacturing, Petroleum and Coal Products Manufacturing, the Pulp, Paper, and Paperboard Mills Industries, Metal Ore Mining, and the Iron and Steel and Ferroalloy Manufacturing Industries?
(a) Definitions. All terms not defined in this paragraph (a) shall have the meaning given to them in the Act and in subpart A of 40 CFR part 60.
Affected unit means an industrial boiler meeting the applicability criteria of this section.
Boiler means an enclosed device using controlled flame combustion and having the primary purpose of recovering thermal energy in the form of steam or hot water. Controlled flame combustion refers to a steady-state, or near steady-state, process wherein fuel and/or oxidizer feed rates are controlled.
Coal means “coal” as defined in 40 CFR 60.41b.
Distillate oil means “distillate oil” as defined in 40 CFR 60.41b.
Maximum heat input capacity means means the ability of a steam generating unit to combust a stated maximum amount of fuel on a steady state basis, as determined by the physical design and characteristics of the steam generating unit.
Natural gas means “natural gas” as defined in 40 CFR 60.41.
Operating day means a 24-hour period between 12:00 midnight and the following midnight during which any fuel is combusted at any time in the steam generating unit. It is not necessary for fuel to be combusted continuously for the entire 24-hour period.
Residual oil means “residual oil” as defined in 40 CFR 60.41c.
(b) Applicability. (1) The requirements of this section apply to each new or existing boiler with a design capacity of 100 mmBtu/hr or greater that receives 90% or more of its heat input from coal, residual oil, distillate oil, natural gas, or combinations of these fuels in the previous ozone season, is located at sources that are within the Basic Chemical Manufacturing industry, the Petroleum and Coal Products Manufacturing industry, the Pulp, Paper, and Paperboard industry, the Metal Ore Mining industry, and the Iron and Steel and Ferroalloys Manufacturing industry and which is located within any of the States listed in § 52.40(c)(2), including Indian country located within the borders of any such State(s). The requirements of this section do not apply to an emissions unit that meets the requirements for a low-use exemption as provided in paragraph (b)(2) of this section.
(2) If you are the owner or operator of a boiler meeting the applicability criteria of paragraph (b)(1) of this section that operates less than 10% per year on an hourly basis, based on the three most recent years of use and no more than 20% in any one of the three years, you are exempt from meeting the emissions limits of this section and are only subject to the recordkeeping and reporting requirements of paragraph (f)(2) of this section.
(i) If you are the owner or operator of an affected unit that exceeds the 10% per year hour of operation over three years or the 20% hours of operation per year criteria, you can no longer comply via the low-use exemption provisions and must meet the applicable emissions limits and other applicable provisions as soon as possible but not later than one year from the date eligibility as a low-use boiler was negated by exceedance of the low-use boiler criteria.
(ii) [Reserved]
(c) Emissions limitations. If you are the owner or operator of an affected unit, you must meet the following emissions limitations on a 30-day rolling average basis during the 2026 ozone season and in each ozone season thereafter:
(1) Coal-fired industrial boilers: 0.20 lbs NO
(2) Residual oil-fired industrial boilers: 0.20 lbs NO
(3) Distillate oil-fired industrial boilers: 0.12 lbs NO
(4) Natural gas-fired industrial boilers: 0.08 lbs NO
(5) Boilers using combinations of fuels listed in paragraphs (c)(1) through (4) of this section: such units shall comply with a NO
(d) Testing and monitoring requirements. (1) If you are the owner or operator of an affected unit, you shall conduct an initial compliance test as described in 40 CFR 60.8 using the continuous system for monitoring NO
(i) For the initial compliance test, you shall monitor NO
(ii) You are not required to conduct an initial compliance test if the affected unit is subject to a pre-existing, federally enforceable requirement to monitor its NO
(2) If you are the owner or operator of an affected unit with a heat input capacity of 250 mmBTU/hr or greater, you are subject to the following monitoring requirements:
(i) You shall install, calibrate, maintain, and operate a continuous emissions monitoring system (CEMS) for measuring NO
(ii) You shall operate the CEMS and record data during all periods of operation during the ozone season of the affected unit except for CEMS breakdowns and repairs. You shall record data during calibration checks and zero and span adjustments.
(iii) You shall express the 1-hour average NO
(iv) Following the date on which the initial compliance test is completed, you shall determine compliance with the applicable NO
(v) You shall follow the procedures under 40 CFR 60.13 for installation, evaluation, and operation of the continuous monitoring systems. Additionally, you shall use a span value of 1000 ppm NO
(vi) When you are unable to obtain NO
(vii) You may delay installing a CEMS for NO
(3) If you are the owner or operator of an affected unit with a heat input capacity less than 250 mmBTU/hr, you must monitor NO
(i) You must conduct an initial performance test over a minimum of 24 consecutive steam generating unit operating hours at maximum heat input capacity to demonstrate compliance with the NO
(ii) You must conduct annual performance tests once per calendar year to demonstrate compliance with the NO
(iii) You must develop and comply with a monitoring plan that relates the operational parameters to emissions of the affected unit. The owner or operator of each affected unit shall develop a monitoring plan that identifies the operating conditions of the affected unit to be monitored and the records to be maintained in order to reliably predict NO
(A) You shall identify the specific operating parameters to be monitored and the relationship between these operating parameters and the applicable NO
(B) You shall include the data and information used to identify the relationship between NO
(C) You shall identify: how these operating parameters, including steam generating unit load, will be monitored on an hourly basis during periods of operation of the affected unit; the quality assurance procedures or practices that will be employed to ensure that the data generated by monitoring these operating parameters will be representative and accurate; and the type and format of the records of these operating parameters, including steam generating unit load, that you will maintain.
(4) You shall submit the monitoring plan to the EPA via the CEDRI reporting system, and request that the relevant permitting agency incorporate the monitoring plan into the facility's title V permit.
(e) Recordkeeping requirements. (1) If you are the owner or operator of an affected unit, which is not a low-use boiler, you shall maintain records of the following information for each day the affected unit operates during the ozone season:
(i) Calendar date;
(ii) The average hourly NO
(iii) The 30-day average NO
(iv) Identification of the affected unit operating days when the calculated 30-day rolling average NO
(v) Identification of the affected unit operating days for which pollutant data have not been obtained, including reasons for not obtaining sufficient data and a description of corrective actions taken;
(vi) Identification of the times when emissions data have been excluded from the calculation of average emissions rates and the reasons for excluding data;
(vii) Identification of “F” factor used for calculations, method of determination, and type of fuel combusted;
(viii) Identification of the times when the pollutant concentration exceeded full span of the CEMS;
(ix) Description of any modifications to the CEMS that could affect the ability of the CEMS to comply with Performance Specification 2 or 3 in appendix B to 40 CFR part 60;
(x) Results of daily CEMS drift tests and quarterly accuracy assessments as required under Procedure 1 of 40 CFR part 60, appendix F; and
(xi) The type and amounts of each fuel combusted.
(2) If you are the owner or operator of an affected unit complying as a low-use boiler, you must maintain the following records consistent with the requirements of § 52.40(g):
(i) Identification and location of the boiler;
(ii) Nameplate capacity;
(iii) The fuel or fuels used by the boiler;
(iv) For each operating day, the type and amount of fuel combusted, and the date and total number of hours of operation; and
(v) the annual hours of operation for each of the prior 3 years, and the 3-year average hours or operation.
(f) Reporting requirements. (1) If you are the owner or operator of an affected unit, you must submit the results of the performance test or performance evaluation of the CEMS following the procedures specified in § 52.40(g) within 60 days after the date of completing each performance test required by this section.
(2) If you are the owner or operator of an affected unit, you are required to submit excess emissions reports for any excess emissions that occurred during the reporting period. Excess emissions are defined as any calculated 30-day rolling average NO
(3) If you are the owner or operator an affected unit subject to the continuous monitoring requirements for NO
(4) If you are the owner or operator of an affected unit, you shall submit an annual report in PDF format to the EPA by January 30th of each year via CEDRI or analogous electronic reporting approach provided by the EPA to report data required by this section. Annual reports shall be submitted following the procedures in § 52.40(g).