View all text of Subpart 62.35 [§ 62.35-1 - § 62.35-50]

§ 62.35-50 - Tabulated monitoring and safety control requirements for specific systems.

The minimum instrumentation, alarms, and safety controls required for specific types of systems are listed in Table 62.35-50.

Table 62.35-50—Minimum System Monitoring and Safety Control Requirements for Specific Systems (Note 1)

System Service Instrumentation Alarm Safety control Notes Main (Propulsion) boiler( 1)( 1)( 1)(2) Supply casing and uptakesFire Burner flameStatusFailureBurner auto trip(3) Burner seatingFailure......ditto(3) Trial for ignitionStatusFailure......ditto Control powerAvailable (pressure)Failure (low)......ditto(3) Manual trip(3) Burner valveOpen/closed Low fire interlockStatus Program control interlockStatus Main (Propulsion steam) turbine( 2)( 2)( 2)(4, 5) Manual trip Main propulsion, diesel( 1)( 1)( 1)(4, 5) Manual trip Main propulsion, remote controlFailure......ditto Auto safety trip overrideActivated Starting powerPressure (voltage)LowLimit(2) Location in controlStatusOverride(6) Shaft speed/direction/pitch( 3)( 3)( 3) Clutch fluidPressureLow Main propulsion, electric( 4)( 4)( 4)( 4)(7) Main propulsion, shaftingStern tube oil tank levelLow Line shaft bearingTemperatureHigh Forced lubrication PressureLow Main propulsion, controllable pitch propellerHydraulic oilPressureHigh, Low TemperatureHigh GeneratorsShip service( 1)( 1) Starting pressure/voltageLow Tripped Emergency( 5)( 5)( 5) Turbogenerator( 1 6)( 1 6)( 6) Manual trip Diesel( 1 7)( 1 7)( 7)(5) Manual trip Auxiliary boilerRunTrip(12) Gas turbine( 8)( 8)( 8)( 8)(5) Engines and turbinesJacking/turning gearEngaged(8) Fuel oil( 9)( 9)( 9) Remote/auto fill levelHighAuto trip or overflow arrangement Hi. press. leakage levelHigh BilgePump remote controlRun Pump auto controlRunExcessive operations LevelHigh/location Machinery space CL.3 W.T. doorsOpen/closed Fire detectionMachinery spacesSpace on fire(9) Fire mainPressureLow PersonnelDeadmanFail to acknowledge(10) General, control and alarm systemsPower supplyAvailable (pressure)Failure (low) System functionFailure(11) Console air conditioningFailure Built in test equipmentActive Sequential interlockActivated Safety controlActivatedAuto trip/limit(11) Redundant auxiliary, system, power supplyStatusAuto transfer

1 See the ABS Steel Vessel Rules (incorporated by reference; see 46 CFR 62.05-1) Part 4-9-4, tables 7A and 8.

2 See ABS Steel Vessel Rules Part 4-9-4, tables 7A and 8.

3 See § 113.37 of this chapter.

4 See subparts 111.33 and 111.35 of this chapter.

5 See subparts 112.45 and 112.50 of this chapter.

6 See § 111.12-1(c) of this chapter.

7 See § 111.12-1 (b), (c) of this chapter.

8 See ABS Steel Vessel Rules Part 4-9-4, Table 8; and 46 CFR 58.10-15(f).

9 See ABS Steel Vessel Rules Part 4-9-4, tables 7A and 8.

Notes on Table 62.35-50:

1. The monitoring and controls listed in this table are applicable if the system listed is provided or required.

2. Safety limit controls must be provided in navigating bridge primary propulsion control systems. See § 62.35-5(c).

3. Safety trip controls and alarms must be provided for all main boilers, regardless of mode of operation. See § 62.35-20(a).

4. Loss of forced lubrication safety trip controls must be provided, as applicable.

5. Override of overspeed and loss of forced lubrication pressure safety trip controls must not be provided. See § 62.35-5(e)(2).

6. Transfer interlocks must be provided.

7. Semiconductor controlled rectifiers must have current limit controls.

8. Interlocks must be provided. See § 62.25-5(a).

9. Main and remote control stations, including the navigational bridge, must provide visual and audible alarms in the event of a fire in the main machinery space.

10. See § 62.50-20(b)(1).

11. Alarms and controls must be failsafe. See § 62.30-1.

12. Vital auxiliary boilers only. Also see part 63.

[CGD 81-030, 53 FR 17838, May 18, 1988; 53 FR 19090, May 26, 1988, as amended by USCG-2000-7790, 65 FR 58461, Sept. 29, 2000; USCG-2003-16630, 73 FR 65190, Oct. 31, 2008]