§ 111.05-31 - Grounding conductors for systems.

(a) A conductor for grounding a direct-current system must be the larger of:

(1) The largest conductor supplying the system; or

(2) No. 8 AWG (8.4mm 2).

(b) A conductor for grounding the neutral of an alternating-current system must meet Table 111.05-31(b).

Table 111.05-31(b)—Neutral Grounding Conductor for Alternating-Current System

Size of the largest generator cable or equivalent for parallel generators—AWG-MCM (mm 2) Size of the system grounding conductor—AWG(mm 2) Greater than Less than or equal to 2 (33.6)8 (8.4) 2 (33.6)0 (53.5)6 (13.3) 0 (53.5)3/0 (85.0)4 (21.2) 3/0 (85.0)350 MCM (177)2 (33.6) 350 MCM (177)600 MCM (304)0 (53.5) 600 MCM (304)1100 MCM (557)2/0 (67.5) 1100 MCM (557)3/0 (85.0)