View all text of Subpart Da [§ 60.40Da - § 60.52Da]
§ 60.43Da - Standards for sulfur dioxide (SO2).
(a) On and after the date on which the initial performance test is completed or required to be completed under § 60.8, whichever date comes first, no owner or operator subject to the provisions of this subpart shall cause to be discharged into the atmosphere from any affected facility which combusts solid fuel or solid-derived fuel and for which construction, reconstruction, or modification commenced before or on February 28, 2005, except as provided under paragraphs (c), (d), (f) or (h) of this section, any gases that contain SO
(1) 520 ng/J (1.20 lb/MMBtu) heat input and 10 percent of the potential combustion concentration (90 percent reduction);
(2) 30 percent of the potential combustion concentration (70 percent reduction), when emissions are less than 260 ng/J (0.60 lb/MMBtu) heat input;
(3) 180 ng/J (1.4 lb/MWh) gross energy output; or
(4) 65 ng/J (0.15 lb/MMBtu) heat input.
(b) On and after the date on which the initial performance test is completed or required to be completed under § 60.8, whichever date comes first, no owner or operator subject to the provisions of this subpart shall cause to be discharged into the atmosphere from any affected facility which combusts liquid or gaseous fuels (except for liquid or gaseous fuels derived from solid fuels and as provided under paragraphs (e) or (h) of this section) and for which construction, reconstruction, or modification commenced before or on February 28, 2005, any gases that contain SO
(1) 340 ng/J (0.80 lb/MMBtu) heat input and 10 percent of the potential combustion concentration (90 percent reduction); or
(2) 100 percent of the potential combustion concentration (zero percent reduction) when emissions are less than 86 ng/J (0.20 lb/MMBtu) heat input.
(c) On and after the date on which the initial performance test is completed or required to be completed under § 60.8, whichever date comes first, no owner or operator subject to the provisions of this subpart shall cause to be discharged into the atmosphere from any affected facility which combusts solid solvent refined coal (SRC–I) any gases that contain SO
(d) Sulfur dioxide emissions are limited to 520 ng/J (1.20 lb/MMBtu) heat input from any affected facility which:
(1) Combusts 100 percent anthracite;
(2) Is classified as a resource recovery unit; or
(3) Is located in a noncontinental area and combusts solid fuel or solid-derived fuel.
(e) Sulfur dioxide emissions are limited to 340 ng/J (0.80 lb/MMBtu) heat input from any affected facility which is located in a noncontinental area and combusts liquid or gaseous fuels (excluding solid-derived fuels).
(f) The SO
(g) Compliance with the emission limitation and percent reduction requirements under this section are both determined on a 30-day rolling average basis except as provided under paragraph (c) of this section.
(h) When different fuels are combusted simultaneously, the applicable standard is determined by proration using the following formula:
(1) If emissions of SO
(2) If emissions of SO
(i) Except as provided in paragraphs (j) and (k) of this section, on and after the date on which the initial performance test is completed or required to be completed under § 60.8, whichever date comes first, no owner or operator of an affected facility for which construction, reconstruction, or modification commenced after February 28, 2005, but before May 4, 2011, shall cause to be discharged into the atmosphere from that affected facility, any gases that contain SO
(1) For an affected facility which commenced construction, any gases that contain SO
(i) 180 ng/J (1.4 lb/MWh) gross energy output; or
(ii) 5 percent of the potential combustion concentration (95 percent reduction).
(2) For an affected facility which commenced reconstruction, any gases that contain SO
(i) 180 ng/J (1.4 lb/MWh) gross energy output;
(ii) 65 ng/J (0.15 lb/MMBtu) heat input; or
(iii) 5 percent of the potential combustion concentration (95 percent reduction).
(3) For an affected facility which commenced modification, any gases that contain SO
(i) 180 ng/J (1.4 lb/MWh) gross energy output;
(ii) 65 ng/J (0.15 lb/MMBtu) heat input; or
(iii) 10 percent of the potential combustion concentration (90 percent reduction).
(j) On and after the date on which the initial performance test is completed or required to be completed under § 60.8, whichever date comes first, no owner or operator of an affected facility that commenced construction, reconstruction, or modification commenced after February 28, 2005, and that burns 75 percent or more (by heat input) coal refuse on a 12-month rolling average basis, shall caused to be discharged into the atmosphere from that affected facility any gases that contain SO
(1) For an affected facility for which construction commenced after February 28, 2005, any gases that contain SO
(i) 180 ng/J (1.4 lb/MWh) gross energy output on a 30-day rolling average basis; or
(ii) 6 percent of the potential combustion concentration (94 percent reduction) on a 30-day rolling average basis.
(2) For an affected facility for which reconstruction commenced after February 28, 2005, any gases that contain SO
(i) 180 ng/J (1.4 lb/MWh) gross energy output on a 30-day rolling average basis;
(ii) 65 ng/J (0.15 lb/MMBtu) heat input on a 30-day rolling average basis; or
(iii) 6 percent of the potential combustion concentration (94 percent reduction) on a 30-day rolling average basis.
(3) For an affected facility for which modification commenced after February 28, 2005, any gases that contain SO
(i) 180 ng/J (1.4 lb/MWh) gross energy output on a 30-day rolling average basis;
(ii) 65 ng/J (0.15 lb/MMBtu) heat input on a 30-day rolling average basis; or
(iii) 10 percent of the potential combustion concentration (90 percent reduction) on a 30-day rolling average basis.
(k) On and after the date on which the initial performance test is completed or required to be completed under § 60.8, whichever date comes first, no owner or operator of an affected facility located in a noncontinental area for which construction, reconstruction, or modification commenced after February 28, 2005, but before May 4, 2011, shall cause to be discharged into the atmosphere from that affected facility any gases that contain SO
(1) For an affected facility that burns solid or solid-derived fuel, the owner or operator shall not cause to be discharged into the atmosphere any gases that contain SO
(2) For an affected facility that burns other than solid or solid-derived fuel, the owner or operator shall not cause to be discharged into the atmosphere any gases that contain SO
(l) Except as provided in paragraphs (j) and (m) of this section, on and after the date on which the initial performance test is completed or required to be completed under § 60.8, whichever date comes first, no owner or operator of an affected facility for which construction, reconstruction, or modification commenced after May 3, 2011, shall cause to be discharged into the atmosphere from that affected facility, any gases that contain SO
(1) For an affected facility which commenced construction or reconstruction, any gases that contain SO
(i) 130 ng/J (1.0 lb/MWh) gross energy output; or
(ii) 140 ng/J (1.2 lb/MWh) net energy output; or
(iii) 3 percent of the potential combustion concentration (97 percent reduction).
(2) For an affected facility which commenced modification, any gases that contain SO
(i) 180 ng/J (1.4 lb/MWh) gross energy output; or
(ii) 10 percent of the potential combustion concentration (90 percent reduction).
(m) On and after the date on which the initial performance test is completed or required to be completed under § 60.8, whichever date comes first, no owner or operator of an affected facility located in a noncontinental area for which construction, reconstruction, or modification commenced after May 3, 2011, shall cause to be discharged into the atmosphere from that affected facility any gases that contain SO
(1) For an affected facility that burns solid or solid-derived fuel, the owner or operator shall not cause to be discharged into the atmosphere any gases that contain SO
(2) For an affected facility that burns other than solid or solid-derived fuel, the owner or operator shall not cause to be discharged into the atmosphere any gases that contain SO